Energy Saving Devices
The KVAR PFC UNIT is designed specifically for motor run applicaitons. They may be used on 50/60 Hertz systems.
Single Phase/three phase
220 Volt AC Single Phase and 480 Volt AC Three Phase applications
Withstands surges to 480 VAC
Self-healing metallized capacitors
Low losses, 0.5 watt per kVAR
UL Recognized Pressure Sensitive Interrupter
Interrupter for maximum 10,000 amp fault currents
Discharge system to reduce voltage to 50 volts or less within 1 minute of de-energization . Case rupture protection: Internal pressure sensitive devices incorporated to activate at end of life or misapplication.
Operating temperature range of -40° C to +90° C
Flashpoint: + 182 degree C to + 200 degree C
UL Listed and CSA Approved
Values +/- 2% of rating
Hermetically sealed aluminum case with turn plate steel cover
Phenolic insulating bushings
Box size 6” x 6” x 4” up to 12” x 12” x12”
Operating Life: 60,000 hours with 95% survival
General Enclosure: NEMA 3R Indoor/Outdoor
Wire Rating: 600 Volts, THHN or MTW or THWN or AWM, Gasoline & Oil Resistant 11.
Waste Disposal: Dispose of in accordance with all local, federal, and foreign regulations, Component liquid is bio safe.